Timing verification (ig mode), Functional test report, Pickup verification (phase mode) – Basler Electric BE1-11m User Manual

Page 358

Advertising
background image

346

9424200996 Rev L

Step 8: (Optional.) Repeat steps 1 through 7 for settings group 1, 2, and 3.

Step 9: (Optional.) Repeat steps 1 through 8 for 50-2, 50-3, 50-4, 50-5, and 50-6.

Step 10: (Optional.) Repeat steps 1 through 9 with CT Circuit 2 as the source for protection systems

equipped with two sets of CTs. In step 5, replace D1 with F1, D2 with F2, etc.

Timing Verification (IG Mode)

Step 1: Use BESTCOMSPlus to open the Protection, Current, Instantaneous Overcurrent (50-1) screen

and send the first row of test settings in Table 142 to the BE1-11m for settings group 0.

Table 142. Timing Test Settings (IG Mode)

Pickup Setting

Time Delay

0.5 A

2,000 ms

0.5 A

5,000 ms

0.5 A

10,000 ms

Step 2: Prepare to monitor the 50-1 timings. Timing accuracy is verified by measuring the elapsed time

between a sensing current change and OUT1 closing.

Step 3: Connect and apply 0.45 A to BE1-11m terminals D7 and D8 (IG).

Step 4: Step the ground current up to 0.55 A. Measure the time delay and record the result.

Step 5: Repeat step 4 for the 5,000 ms and 10,000 ms time delay settings of Table 142. Record the

results.

Step 6: (Optional.) Repeat steps 1 through 5 for settings group 1, 2, and 3.

Step 7: (Optional.) Repeat steps 1 through 6 for 50-2, 50-3, 50-4, 50-5, and 50-6.

Step 8: (Optional.) Repeat steps 1 through 7 with CT Circuit 2 as the source for protection systems

equipped with two sets of CTs. In step 3, replace D1 with F1, D2 with F2, etc.

Functional Test Report

Pickup Verification (Phase Mode)

Pickup Setting Range = 0.5 to 150 A for 5A sensing

0.1 to 30 A for 1A sensing

Pickup Accuracy =

±2% or ±50 mA, whichever is greater for 5A sensing

±2% or ±10 mA, whichever is greater for 1A sensing

Dropout should occur between 93-99% of the actual pickup value.

Step

Pickup Setting

Low

Actual Pickup

High

Low

*

Actual Dropout

High

*

Pass/Fail

6

0.5 A (5A CT)

0.45 A

0.55 A

0.465 A

0.495 A

P / F

7

5.0 A (5A CT)

4.9 A

5.1 A

4.65 A

4.95 A

P / F

7

20.0 A (5A CT)

20.6 A

20.4 A

18.6 A

19.8 A

P / F

6

0.1 A (1A CT)

0.09 A

0.11 A

0.093 A

0.099 A

P / F

7

1.0 A (1A CT)

0.98 A

1.02 A

0.93 A

0.99 A

P / F

7

4.0 A (1A CT)

3.92 A

4.08 A

3.72 A

3.96 A

P / F

* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.

Instantaneous Overcurrent (50) Test

BE1-11m