Operational settings, N table 76 – Basler Electric BE1-11m User Manual

Page 205

Advertising
background image

9424200996 Rev L

193

Table 76. Logic Output

Name

Logic Function

Purpose

Fuse Loss

Output

True when the 60FL logic is true

Operational Settings

Fuse loss element operational settings are configured on the Fuse Loss (60FL) settings screen (Figure
156)
in BESTCOMSPlus. Settings are summarized in Table 77.

Figure 156. Fuse Loss Settings Screen

Table 77. Operational Settings

Setting

Purpose

Block Voltage Control (51/27)

When enabled and the 60FL logic is true (voltage sensing is lost),
the current tripping level is controlled by the 51 function and the
27R function is inhibited. When enabled and the 60FL logic is
false, the current tripping level is controlled by the 51/27R
function.

Block Phase/V1 Voltage
Elements

All functions that use phase voltage (P) and positive-sequence
voltage (V1) measurements are blocked when the 60FL logic is
true. (27 and 59)

Block 3V0 Voltage Elements

All functions that use the 3-phase residual voltage (3V0)
measurement are blocked when the 60FL logic is true. (59X - 3V0
mode)

Block V2 Voltage Elements

All functions that use the negative-sequence voltage (V2)
measurement are blocked when the 60FL logic is true. (59X - V2
mode)

Block Power/Power Factor
Elements

All functions that use the power measurements are blocked when
the 60FL logic is true. (32 and 55)

Ignore Breaker Status

When enabled, breaker status is ignored.

BE1-11m

Fuse Loss (60FL)

Advertising