Figure 393 – Basler Electric BE1-11m User Manual

Page 570

Advertising
background image

558

9424200996 Rev L

Figure 393. Protection, Current, Current Differential (87) Screen

User Programmable Alarm

User Programmable Alarm 3 is used for reporting a minor alarm, which indicates a large percentage
restraint imbalance during starting mode. Use the Settings Explorer to navigate to Alarm Configuration,
User Programmable Alarms, and name User Programmable Alarm 3 to “Differential Slope”. Navigate to
Alarm Configuration, Alarms, and enable Programmable Alarm 3 as a minor alarm. This alarm will appear
in the sequence of events and alarm reporting as “Differential Slope”.

Instantaneous Undercurrent (37) - Loss of Load Protection

The 37 element protects the motor from overheating by tripping when a load or shaft coupling is lost and
motor current drops. The 37 element protects only when the motor is in running mode and can be set to
trip on a loss of load condition, especially for pump motors where flowing water cools the motor. For
pumps, a loss of current would indicate less cooling. The pickup setting is calculated in Equation 76.

𝑃𝑖𝑐𝑘𝑢𝑝 = 75% 𝑜𝑓 𝐹𝐿𝐴 ∙

1

𝐶𝑇𝑅

= 0.75 ∙ 205 𝐴 ∙

1

60

= 2.563 𝑠𝑒𝑐𝑜𝑛𝑑𝑎𝑟𝑦

Equation 76. 37 Pickup

The Inhibit Level is a low-level setting for when the motor is off and a nuisance trip or alarm is not desired.
Set this setting to 20 percent of FLA as calculated in Equation 77.

𝑃𝑖𝑐𝑘𝑢𝑝 = 20% 𝑜𝑓 𝐹𝐿𝐴 ∙

1

𝐶𝑇𝑅

= 0.20 ∙ 205 𝐴 ∙

1

60

= 0.683 𝐴 𝑠𝑒𝑐𝑜𝑛𝑑𝑎𝑟𝑦

Equation 77. 37 Inhibit Level

Select three-phase mode, set the Pickup setting to 2.563 A, the Inhibit Level to 0.683, and set the Time
Delay to 100 ms (to override load changes) as shown in Figure 394.

Settings Calculation Examples

BE1-11m

Advertising