Rtd biasing and hot/cold safe stall ratio, Overload and trip, And equation 9 – Basler Electric BE1-11m User Manual

Page 111

Advertising
background image

9424200996 Rev L

99

Where:

TCU

end

= Thermal Capacity that the motor will eventually reach if current is maintained at present

magnitude.

τ

= Cooling time constant (either running or stopped)

I

eq

= Equivalent thermal current (zero if IEC Curve is being used)

S

= Overload Pickup setting

SF

= Service Factor setting

FLA

= Full Load Amps setting

TCU = (TCU

start

− TCU

end

)e

−tτ

+ TCU

end

Equation 9. TCU

Where:

TCU

= Present Thermal Capacity

TCU

end

= Thermal Capacity that the motor will eventually reach if current is maintained at present

magnitude.

TCU

start

= Thermal Capacity

T

= Time since last calculation

τ

= Cooling time constant (either running or stopped)

RTD Biasing and Hot/Cold Safe Stall Ratio

The thermal overload curves are based on the assumption of a normal 40

°C ambient and normal motor

cooling. In the case of unusual ambient temperature or blocked or reduced motor cooling, the optional
installed RTDs can be used to improve the estimation of thermal capacity.

The user provides a curve showing RTD thermal capacity used. The curve includes a minimum of three
points and a maximum of 40 points. Three typical points are Ambient RTD Temperature (40

°C) and 0%

TC, Full Load Amps running RTD temperature and thermal capacity, and Maximum Safe Stator RTD
temperature (typically 155

°C).

Equation 10 is used to calculate the Full Load Amp thermal Capacity.

RTD Bias TCU = �1 −

hot safe stall time

cold safe stall time�

Equation 10. RTD Bias TCU

RTD Bias TCU is linearly interpolated when RTD temperature is between defined temperatures.

When the 49TC is in overload and the RTD Bias TCU is higher than the current-based TCU, RTD Bias
TCU is used to update the 49TC thermal capacity. The current based model continues to calculate
thermal capacity from this new bias level. RTD Bias TCU alone will not result in a thermal model trip.
Current must be above the thermal model current pickup.

Overload and Trip

The Overload output occurs first, followed by the Trip output.

Overload

The 49TC pickup level is determined by the Overload setting along with the Service Factor and Full Load
Amps settings located on the System Parameters, Motor Configuration screen in BESTCOMSPlus. The
Overload output becomes true when the equivalent thermal current increases above the pickup current. In
BESTlogicPlus, the Overload output can be connected to other logic elements to annunciate the
condition, control other elements in logic, and start the fault recorder (logic element FAULTTRIG).

Assertion of the Overload output initiates a timer that begins timing to a thermal trip. The duration of the
timer is established by the thermal curve.

BE1-11m

Thermal Curve (49TC) Protection

Advertising