Figure 367. Single-Line Drawing, Phase Differential Protection (5,000 HP Synchronous Motor Example)

Motor Manufacturer Data

Motor manufacturer data should be reviewed before configuring the BE1-11m. Typical motor
manufacturer data is listed below.

GENERAL

HP .....................................................................5000 HP

System Frequency ............................................60 Hz

Motor Rotation ..................................................1200 RPM

Bus Voltage ......................................................12 kV

Full-Load Amps (FLA, Synchronous) ...............205 A

Full-Voltage No-Load Stator Current in Sync ...128 A (no excitation)

Full-Voltage Line Current (95% Speed) ...........392 A (no excitation)

Maximum Locked Rotor Current (Max. LRA) ...755 A

Service Factor...................................................1.15

Power Factor Minimum .....................................0.90

Stator Insulation Class ......................................F (155

°C per NEMA MG-1 Standard)

Ambient Temperature Rating ...........................40

°C

Stator Temperature Rise ..................................76

°C

Subtransient Reactance Xd” .............................0.368 pu, 4263 kVA base

Hot Safe Stall Time ...........................................8.5 seconds

Cold Safe Stall Time .........................................10.7 seconds

12-kV Bus

52

M

2 or 3 PTs

R

T

D

3 CTs

3 CTs

P

0

0

6

9

-6

5

BE1-11m

Settings Calculation Examples