514

9424200996 Rev L

Physical

Weight ........................................ 2.15 lb (0.975 kg)
IP Class ...................................... IP50
Size ............................................ Refer to Mounting.

Repair

RTD modules are manufactured using state-of-the-art surface-mount technology. As such, Basler Electric
recommends that no repair procedures be attempted by anyone other than Basler Electric personnel.

Before returning the RTD module for repair, contact the Basler Electric Technical Services Department at
618-654-2341 for a return authorization number.

Maintenance

Preventive maintenance consists of periodically checking that the connections between the RTD module
and the system are clean and tight.

Storage

This device contains long-life aluminum electrolytic capacitors. For devices that are not in service (spares
in storage), the life of these capacitors can be maximized by energizing the device for 30 minutes once
per year.