9424200996 Rev L

421

Figure 281. Integrating Timer Mode

Latched Mode

Step 1: Use BESTCOMSPlus to send the operational settings in Table 186 to the BE1-11m. Retain the

logic settings from Figure 276.

Table 186. Operational Settings (Latched Mode)

Setting

Value

BESTCOMSPlus Screen

Description

62-1 Mode

Latched

Control, Logic Timers (62)

Sets 62-1 to One-
Shot/Retriggerable mode

62-1 Time Delay
1 (T1)

30,000
ms

Control, Logic Timers (62)

Sets 62-1 pickup time delay to
15,000 ms

62-1 Time Delay
2 (T2)

0

Control, Logic Timers (62)

Sets 62-1 dropout time delay to 0

43-1 Mode

Pulse

Control, Virtual Control
Switches (43)

Sets 43-1 to Pulse mode

43-2 Mode

Pulse

Control, Virtual Control
Switches (43)

Sets 43-2 to Pulse mode

62-1 Target

Enabled

Target Configuration, Targets
screen.

Enables 62-1 target

Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 282.

62-1 initiates when 43-1 output is true.

62-1 is blocked when 43-2 output is true.

OUT1 closes when 62-1 output is true.

Step 3: Step 5 supplies the 62-1 timer with a latch input by pulsing the 43-1 switch from an OFF state to

an ON state and then back to an OFF state. These commands also supply a block input when
the 43-2 is ON. You can view the state changes of the 43-1 switch at the Metering > Control >
Virtual Switches screen on the front-panel display.

Step 4: Close communication with BESTCOMSPlus.

P

0

0

3

5

-3

4

0

2

-2

7

-0

6

62-x

Block

Initiate

100%

0%

Timer

BE1-11m

Logic Timers (62) Test