Table – Basler Electric BE1-11m User Manual

Page 599

Advertising
background image

9424200996 Rev L

587

Firmware

Version and Date

Change

2.08.02, Aug-14

Added missing characters to scrolled metering screen

Corrected shifted HMI screen headings for Watts/vars, VA/PF,
and Dip/Swell

Corrected unsecured access on non BESTCOMSPlus ports

Made default state of 61850 inputs available at all times

Corrected intermittent detection of Start/Stop button being
pressed.

Improved IRIG accuracy

Corrected the function of the Block input for Analog Input
Protection elements

Improved display of oscillographic records for 3W and 4W
configurations

Removed blank screen from scrolling metering when 6 metering
values are selected

Corrected uploading of a blank CID file for 61850

Table 204. BESTCOMSPlus

® Software Revision History

Software

Version and Date

Change

2.08.00, Aug-10

Initial release

2.08.01, Oct-10

Improved Off-Page logic

2.10.02, Jun-11

Added the ability to select what data to view/export from the
Preview Metering and Export Metering buttons

Added the ability to save workspace

Added the ability to auto reconnect when connection is lost

Added the ability to close multiple views

Enhanced BESTlogicPlus

2.11.01, Nov-11

Added Output Override Alarm settings

Added IRIG Decoding setting on Clock Setup screen

Added 1A setting range for Full Load Amps and IEC Hot Curve
Current settings of 49TC element

Enhanced voltage settings resolution for 27, 59, and 81
elements

Enhanced settings file printout

Added Thermal Capacity Reset button on Motor Meter screen

2.11.02, Dec-11

Improved metering and settings file printouts

Added options to print Modbus and DNP points in settings file
printouts

Improved Phasor Diagrams in Metering

2.13.00, Apr-12

Maintenance release

2.14.00, Jul-12

Maintenance release

3.00.02, Sep-12

Added support for BE1-11m firmware version 2.06.00

Updated the settings compare feature to include Modbus

™ and

DNP differences

3.01.01, Nov-12

Maintenance release

3.02.00, Dec-12

Added Windows 8 compatibility

3.03.00, Mar-13

Maintenance release

3.03.03, Jun-13

Updated PC requirements (See the BESTCOMSPlus chapter for
more information.)

3.04.00, Aug-13

Added default fixed 0 on logic block inputs in BESTlogicPlus

3.04.01, Oct-13

Maintenance release

3.05.02, Dec-13

Added support for BE1-11m firmware version 2.07.00

Added a feature to reset the BE1-11m to factory defaults

BE1-11m

Revision History

Advertising