Timing verification – Basler Electric BE1-11m User Manual

Page 396

Advertising
background image

384

9424200996 Rev L

Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus Programmable Logic shown in Figure

265.

Blocking is disabled.

OUT1 closes for 40Q Trip.

OUT2 closes for 40Q Pickup.

Fault recording is enabled.

Figure 265. BESTlogicPlus Settings

Step 3: Use BESTCOMSPlus to open the Protection, Power, Loss of Excitation - Reverse Var Based

(40Q) screen and send the first row of test settings in Table 170 to the BE1-11m.

Table 170. Pickup Test Settings

Pickup Setting

Time Delay

500 var

50 ms

1,000 var

50 ms

2,000 var

50 ms

Step 4: Connect and apply a 100 Vac, three-phase voltage source at nominal frequency to terminals

C13 (A-phase), C14 (B-phase), C15 (C-phase), and C16 (Neutral). Connect a variable ac
current source to terminals D1 (A-phase polarity) and D2 (A-phase non-polarity).

Step 5: Set A-phase current to lag the voltage by 90 degrees and slowly increase the current from

0 amps until OUT2 closes and record the pickup. Verify the 40Q target on the front-panel
display. Decrease the A-phase current until OUT2 opens and record the dropout.

Step 6: With the BE1-11m picked up (OUT2 closed), change the angle of the applied current to

90 degrees I lag E and verify that OUT2 opens. This verifies that the 40Q function is operating
on leading var.

Step 7: Repeat steps 5 and 6 for the 1,000 var and 2,000 var pickup settings in Table 170. Record the

results.

Step 8: (Optional.) Repeat steps 1 through 7 for settings group 1, 2, and 3.

Timing Verification

Step 1: Use BESTCOMSPlus to open the Protection, Power, Loss of Excitation - Reverse Var Based

(40Q) screen and send the first row of test settings in Table 171 to the BE1-11m for settings
group 0.

Table 171. Timing Test Settings

Pickup Setting

Time Delay

500 var

2,000 ms

500 var

5,000 ms

500 var

10,000 ms

Loss of Excitation - Reverse Var Based (40Q) Test

BE1-11m

Advertising