Basler Electric BE1-11m User Manual

Page 386

Advertising
background image

374

9424200996 Rev L

Setting

Value

BESTCOMSPlus Screen

Description

Phase VT
Ratio

1

System Parameters, Sensing
Transformers

Sets phase VT ratio to 1

Phase VT
Connection

4W-Y

System Parameters, Sensing
Transformers

Sets phase VT connection to
4W-Y

27/59 Mode

PN

System Parameters, Sensing
Transformers

Sets 27/59 mode to phase-
neutral

Circuit 1 Tap

2.00

System Parameters, Sensing
Transformers

Sets the tap for circuit 1 to 2.00
A secondary

Circuit 2 Tap

2.00

System Parameters, Sensing
Transformers

Sets the tap for circuit 2 to 2.00
A secondary

Mode

Percent
Differential

Protection, Current, Phase
Differential (87)

Sets the type of operation
protection to traditional phase
current differential

Slope Mode

Average

Protection, Current, Phase
Differential (87)

Sets the element to operate
using average restraint current

Min. Rest.
Pickup (MOT)

0.10

Protection, Current, Phase
Differential (87)

Sets the minimum amount of
operate current required for a
trip to 0.10x tap

Restraint
Slope 1 (%)

20

Protection, Current, Phase
Differential (87)

Sets the 1

st

slope of the restraint

characteristic to 20%

2

nd

Slope

Pickup (MOT)

3.00

Protection, Current, Phase
Differential (87)

The 2

nd

slope is active when the

measured maximum restraint
current is greater 3x tap

Restraint
Slope 2 (%)

40

Protection, Current, Phase
Differential (87)

Sets the 2

nd

slope of the

restraint characteristic to 40%

Time Delay
(ms)

100

Protection, Current, Phase
Differential (87)

Sets the trip time delay to 100
ms

Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic previously shown in

Figure 263.

Step 3: Prepare to monitor the 87R function operation. Operation can be verified by monitoring OUT2

(see Figure 263).

Step 4: To test the Minimum Restrained Pickup setting, connect two balanced three-phase current

sources to the BE1-11m in ABC rotation: 0.5

∠0°, 0.5∠–120°, 0.5∠120° amps to terminals D1

through D6 and 0.5

∠180°, 0.5∠60°, 0.5∠–60° amps to terminals F1 through F6 (0.25x tap).

Step 5: Slowly increase the A-phase current in CT circuit 1 or 2 until OUT2 closes and record the

pickup. This should occur at 0.70 A

±0.05 A. Verify that there is an 87A target on the front-panel

display.

Step 6: Slowly decrease the A-phase current in CT circuit 1 or 2 until OUT2 reopens and record the

dropout. See the functional test report for acceptable ranges.

Step 7: Reset to the current levels in step 5 and reset all targets.

Step 8: Slowly decrease the A-phase current in CT circuit 1 or 2 until OUT2 closes and record the

pickup. This should occur at 0.30 A

±0.05 A. Verify that there is an 87A target on the front-panel

display.

Step 9: Slowly increase the A-phase current in CT circuit 1 or 2 until OUT2 reopens and record the

dropout. See the functional test report for acceptable ranges.

Phase Current Differential (87) Test

BE1-11m