Specifications, Operating power, Analog inputs – Basler Electric BE1-11m User Manual

Page 523: Rtd inputs

Advertising
background image

9424200996 Rev L

511

Figure 336. RTD Type Selection Screen

The source for the 49RTD protection elements can be set for RTD Group 1, 2, 3, 4, 5, 6, or 7. Refer to the

Resistance Temperature Detector (49RTD) Protection

chapter for information on setting 49RTD

protection elements.

Figure 337. RTD Configuration Block Screen

Specifications

Operating Power

Nominal ...................................... 125/250 Vac/dc
Range ......................................... 90 to 270 Vac or 90 to 300 Vdc
Maximum Consumption ............. 9 W

Analog Inputs

The RTD module contains four programmable analog inputs.
Rating ......................................... 4 to 20 mAdc or 0 to 10 Vdc (user-selectable)

RTD Inputs

The RTD module contains 12 programmable RTD inputs.
User-Selectable Types ............... 100

Ω Platinum (DIN43760), 10 Ω Copper, 100 Ω Nickel, or 120 Ω Nickel

Range .........................................

–50 to 250°C (–58 to 482°F)

Accuracy.....................................

±2°C (3.6°F)

Maximum Lead Length ............... 150 feet (4.25 km) with 22 AWG (0.326 mm

2

) wire

Sensing Current Level ................ 2.5 mA
Isolation ...................................... 35 Vpp

BE1-11m

RTD Module