Figure 354 – Basler Electric BE1-11m User Manual

Page 540

Advertising
background image

528

9424200996 Rev L

Figure 354. Protection, Current, Instantaneous Overcurrent (50-3) Screen

Instantaneous Overcurrent (50-4) - Overload Protection

The 50-4 element is used for overload protection while the motor is running. This protection is configured
according to the service factor of the motor. The pickup setting should be 115 to 125 percent of the
service factor per IEEE C37.96-2000, IEEE Guide for AC Motor Protection. If the service factor is 1.0,
then overload pickup should be 115 percent of FLA. The pickup setting should be 130 percent of FLA for
a service factor of 1.15. If the service factor is unknown, use 1.0. In this example, the service factor is 1.0
and the pickup setting is calculated using Equation 46. Secondary full load amps is calculated in Equation
38.

π‘ƒπ‘–π‘π‘˜π‘’π‘ = 𝐹𝐿𝐴

π‘†π‘’π‘π‘œπ‘›π‘‘π‘Žπ‘Ÿπ‘¦

βˆ™ 1.15 = 4.54 βˆ™ 1.15 = 5.221 𝐴 π‘ π‘’π‘π‘œπ‘›π‘‘π‘Žπ‘Ÿπ‘¦

Equation 46. 50-4 Pickup

A delay is used to prevent the BE1-11m from operating under temporary overloads while the motor is
running. Typically, the delay is set short, but can be set longer if the process is significant or if an operator
is regulating the load. The NEMA MG-1 standard states that β€œa large induction motor can withstand an
occasional overload of 1.5

β€’ FLA for 30 seconds.” A conservative time delay (using a factor of 1) is

calculated in Equation 47. The hot safe stall time is found in the motor manufacturer data.

π‘‡π‘–π‘šπ‘’ π·π‘’π‘™π‘Žπ‘¦ = 1 βˆ™ π»π‘œπ‘‘ π‘†π‘Žπ‘“π‘’ π‘†π‘‘π‘Žπ‘™π‘™ π‘‡π‘–π‘šπ‘’ (9 𝑠) = 9 π‘ π‘’π‘π‘œπ‘›π‘‘π‘ 

Equation 47. 50-4 Time Delay

Select three-phase mode, set the Pickup setting to 5.221 A, and set the Time Delay to 9 seconds as
shown in Figure 355.

Figure 355. Protection, Current, Instantaneous Overcurrent (50-4) Screen

Instantaneous Overcurrent (50-5) - Jam Protection

The 50-5 element is used for jam protection while the motor is running. It protects the motor when the
load torque exceeds the torque capacity of the motor. This condition develops motor current equal to or

Settings Calculation Examples

BE1-11m

Advertising