Rtd module – Basler Electric BE1-11m User Manual

Page 408

Advertising
background image

396

9424200996 Rev L

Setting

Value

BESTCOMSPlus Screen

Description

Element Mode

Standard
Curve

Protection, Thermal, Thermal
Curve (49TC)

Selects Standard Curve
mode

RTD Biasing

Enabled

Protection, Thermal, Thermal
Curve (49TC)

Enables RTD Biasing

RTD Source

RTD Group 1

Protection, Thermal, Thermal
Curve (49TC)

Selects RTD Group 1
Block

Standard Curve Time
Dial

10

Protection, Thermal, Thermal
Curve (49TC)

Sets Standard Curve
Time Dial to 10

K

0

Protection, Thermal, Thermal
Curve (49TC)

Sets K to 0

Overload

1

Protection, Thermal, Thermal
Curve (49TC)

Sets Overload pickup to
1

Max Emergency
Thermal Capacity

0

Protection, Thermal, Thermal
Curve (49TC)

Sets Max Emergency
Thermal Capacity to 0%

Running Cool Time
Constant

1

Protection, Thermal, Thermal
Curve (49TC)

Sets Running Cool Time
Constant to 1 minute

Stopped Cool Time
Constant

1

Protection, Thermal, Thermal
Curve (49TC)

Sets Stopped Cool Time
Constant to 1 minute

Hot Safe Stall Time

1

Protection, Thermal, Thermal
Curve (49TC)

Sets Hot Safe Stall Time
to 1 second

Cold Safe Stall Time

1

Protection, Thermal, Thermal
Curve (49TC)

Sets Cold Safe Stall Time
to 1 second

49TC

Enabled

Target Configuration, Targets

Enables 49TC target

Step 18: Use BESTCOMSPlus to configure the BESTlogicPlus Programmable Logic shown in Figure

267.

Step 19: Connect a variable resistor and set its value to 120

Ω or connect a fixed 120 Ω resistor to the

RTD1 input on the remote module in three-wire configuration as shown in Figure 269.

Figure 269. RTD1, 3-Wire Connection

Step 20: Navigate to Metering, Motor, RTD Meter on the front-panel display and verify that RTD 1-1 is

approximately 51

°C. This value may be slightly higher or lower depending on the tolerance of

the 120

Ω resistor. The value of RTD 1-1 changes according to the value of the resistor. The

RTD Bias Curve graph in BESTCOMSPlus is used to determine the starting %TC. It is
determined that the starting %TC is 13% for an RTD 1-1 value of 51

°C.

RTD1+

RTD1–

RTD1C

RTD Module

P

0

0

6

1

-4

1

RED

BLACK

BLACK

Thermal Curve (49TC) Test

BE1-11m