Basler Electric BE1-11m User Manual

Page 370

Advertising
background image

358

9424200996 Rev L

Table 150. Operational Settings (3I0 Mode)

Setting

Value

BESTCOMSPlus Screen

Description

Phase CT
Ratio

1

System Parameters, Sensing
Transformers

Sets phase CT ratio to 1

Element
Mode

3I0

Protection, Current, Inverse Overcurrent
(51-1)

Enables 51-1 function for
3I0 mode

Source

CT Circuit 1

Protection, Current, Instantaneous
Overcurrent (51-1)

Selects CT circuit 1 as the
source

51-1
Residual

Enabled

Target Configuration, Targets

Enables residual target for
51-1

Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 260.

Blocking is disabled.

OUT1 closes for 51-1 Trip.

OUT2 closes for 51-1 Pickup.

Fault recording is enabled.

Figure 260. BESTlogicPlus Settings (3I0 Mode)

Step 3: Use BESTCOMSPlus to open the Protection, Current, Inverse Overcurrent (51-1) screen and

send the low range test settings (minimum pickup setting) to the BE1-11m for your sensing input
type in Table 151.

Table 151. Pickup Test Settings (3I0 Mode)

Sensing Input Type

Range

Pickup Setting

Time Dial

5 A

Low

0.5 A

0

Middle

5.0 A

0

High

16.0 A

0

1 A

Low

0.1 A

0

Middle

1.0 A

0

High

3.2 A

0

Step 4: Prepare to monitor the 51-1 function operation. Operation can be verified by monitoring OUT2

(see Figure 260).

Step 5: Connect a current source to terminals D1 and D2 (A-phase).

Step 6: Slowly increase the A-phase current until OUT2 closes and record the pickup. Verify that there

is a 51-1-Residual target on the front-panel display. Slowly decrease the applied current until
OUT2 opens and record the dropout.

Step 7: Repeat step 6 for the middle and high range pickup settings for your sensing input type. Record

the results.

Inverse Overcurrent (51) Test

BE1-11m

Advertising