5. Commissioning

5-10

Festo P.BE-MTR-DCI-CO-EN en 1209a

5.2.2

Setting the reference travel parameters

Notes on referencing to the stop

Note
Damage to components.

The slide may only move directly against a fixed stop if the
maximum permitted impact energy is not exceeded (im-
pact energy = 0.5 x mass x speed

2

).

•

The permitted value can be found in the manual for your
positioning axis.

•

If necessary, reduce the speed at which movement to the
stop is made. The speed can amount to 0 % to 50 % of
the rated speed.

•

During referencing to the stop, set the offset of the axis
zero point

≠

0 (see chapter 5.2.4).

•

Protect sensitive stops by limiting the motor current.

Positioning axis DMES-... can carry out reference travel with
the factory-set current limitation (150 %). The current limita-
tion need not be revised here.

Current limitation

The MTR-DCI recognizes a stop when the maximum motor
current is reached at the same time as the motor is at a
standstill. The maximum motor current during reference
travel can be specified with 10 ... 200 % of the rated motor
current (see help for the FCT or CI object 6073

h

).