5. Commissioning

5-10

Festo P.BE-MTR-DCI-CO-EN en 1209a

5.2.2

Setting the reference travel parameters

Notes on referencing to the stop

Note
Damage to components.

The slide may only move directly against a fixed stop if the
maximum permitted impact energy is not exceeded (im-
pact energy = 0.5 x mass x speed

2

).

The permitted value can be found in the manual for your
positioning axis.

If necessary, reduce the speed at which movement to the
stop is made. The speed can amount to 0 % to 50 % of
the rated speed.

During referencing to the stop, set the offset of the axis
zero point

0 (see chapter 5.2.4).

Protect sensitive stops by limiting the motor current.

Positioning axis DMES-... can carry out reference travel with
the factory-set current limitation (150 %). The current limita-
tion need not be revised here.

Current limitation

The MTR-DCI recognizes a stop when the maximum motor
current is reached at the same time as the motor is at a
standstill. The maximum motor current during reference
travel can be specified with 10 ... 200 % of the rated motor
current (see help for the FCT or CI object 6073