5. Commissioning

5-63

Festo P.BE-MTR-DCI-CO-EN en 1209a

Overview of parameters involved (see also section B.2.15)

Parameters involved

Description

FCT

PNU

CO/CI

Offset axis zero point

x

1010

607Ch

Reference travel method

x

1011

6098h

Reference travel speeds

x

1012

6099h

Reference travel required

1014

23F6h

Reference travel maximum torque

x

1015

23F7h

Start (FHPP)

CPOS.B2 = positive edge: Start reference travel

Reply message (FHPP)

SPOS.B1 = positive edge: Quit Start
SPOS.B7 = drive referenced

Requirement

Device control by PLC/field bus
Controller must be in status “Operation enabled”
There must not be any command for jogging

Tab. 5/15: Parameters involved in reference travel

Reference travel methods

1)

hex

dec.

Description

17h

23

Search for reference switch in positive direction.

1Bh

27

Search for reference switch in negative direction.

EFh

-17

Search for negative stop. The point found is the reference position. As the
axis must not stand still at the stop, the offset axis zero point must be ≠ 0.

EEh

-18

Search for positive stop. The point found is the reference position. As the
axis must not stand still at the stop, the offset axis zero point must be ≠ 0.

1)

Detailed description of the reference travel methods see section 1.6.3.

Tab. 5/16: Overview of reference travel methods