3. Installation
3-7
Festo P.BE-MTR-DCI-CO-EN en 1209a
3.3
Power supply
3.3.1
Requirements of the power supply
Warning
•
In order to provide the electric power supply, use only
PELV
circuits as per IEC/DIN EN 60204-1 (Protective
Extra-Low Voltage, PELV).
Take into account also the general requirements for
PELV circuits as per IEC/DIN EN 60204-1.
•
Use only power
sourcers which guarantee reliable
electrical isolation of the operating voltage as per
IEC/DIN EN 60204-1.
By the use of PELV power units, protection against electric
shock (protection against direct and indirect contact) is guar-
anteed in accordance with IEC/DIN EN 60204-1 (electrical
equipment of machines, general requirements).
Caution
Damage to the device caused by overvoltage
The voltage inputs of the motor unit have no internal
protection against overvoltage.
•
Make sure that the permitted voltage tolerance is
not exceeded. The tolerance must also be observed
directly at the voltage connections of the MTR-DCI
(see appendix A.1).
•
Install external fuses (see Tab. 3/4).