3. Installation

3-13

Festo P.BE-MTR-DCI-CO-EN en 1209a

3.5

Input for external reference switch

If you are not using a reference switch:

Seal the terminal with the protective cap supplied
(ISK-M8).

Selecting the reference switch:

Use the correct switch type “normally-open contact” in
the PNP variant for the reference switch.

Usea reference switch with screw locking (outer thread
M8x1) at the end of the cable or, as adapter, the connect-
ing cable KM8-M8-... with screw locking.

Use e. g. the following proximity switches from Festo:

Magnetic proximity switches SMT-8M-...

Inductive proximity sensor SIEN-...-M8B-...

When selecting the sensor, note that the accuracy of the
switchover point of the sensor determines the accuracy of
the reference point.

M8x1 socket

Description

1

3

4

1

DC +24 V

DC +24 V voltage output
(only for reference switch)

4

REF

Contact reference switch

3

GND

Ground

Tab. 3/7: Connection REF (reference switch) on the MTR-DCI

The power supply for the reference switch (DC 24 V/Ground)
is provided via pin 1/3.