Festo Электромотор MTR-DCI User Manual

Page 288

Advertising
background image

C. Reference – CANopen and CI objects

C-12

Festo P.BE-MTR-DCI-CO-EN en 1209a

Pre-defined error field

CANopen

1003h

00h...08h

Array

uint32

rw/ro

Description

Error memory for Emergency Object.
The object stores the errors reported by way of the Emergency Object. Each
new error is stored in subindex 01h; the previous errors move one subindex
down each time a new one is added.

Number of errors 1003h

00h

uint32

rw

Number of recorded errors as from subindex 01h.
Value range 0 ... 8
The error field can be cleared by writing “0”.

Standard error

field

1003h

01h

uint32

ro

Last stored error.
The error numbers comprise 16 bits of error code (lower 2 bytes – LSB, see
section 6.5.2, error code in Tab. 6/11) and 16 bits of additional information
(upper 2 bytes – MSB, for MTR-DCI = 0).

Standard error

field

1003h

02h...08h

uint32

ro

Previously stored errors.
See subindex 01h.

COB-ID SYNC message

CANopen

1005h

Var

uint32

rw

Description

COB ID of synchronisation object (SYNC); see DS 301 specification.
Synchronous transfer can be set if the entries in the communication parameters
of the PDOs are modified. For this an entry to this object by the master is essen-
tial; see DS 301 specification.
Default: 128 (0x00000080)

Manufacturer device name

CANopen / CI

1008h

– / 00h

Var

V-string

ro

Description

Type designation of the drive. Example: “MTR-DCI-42S-VCSC-EG7-R2IO”

FHPP

120

1...25

Array

char

ro

Advertising