2 load and logic voltages – Festo Электромотор MTR-DCI User Manual

Page 60

Advertising
background image

3. Installation

3-8

Festo P.BE-MTR-DCI-CO-EN en 1209a

3.3.2

Load and logic voltages

Load voltage

The power electronics and the motor are supplied with direct
current via the voltage connection.

Use the power supply cable KPWR-MC-1-SUB-9HC-... (max
length of 10 m).

Use a closed-loop controlled power unit with high output
reserve and external fuse for the load voltage supply.

Plug

Pin

Colour

1)

Description

A1

A2

A1

black (1)

MTR-DCI-32/42/52:
MTR-DCI-62:

POWER +24 VDC
POWER +48 VDC

A2

black (2)

MTR-DCI-32/42/52/62:

POWER GND

2)

1)

Cable colours with power supply cable KPWR-MC-1-SUB-9HC-...

2)

Do not connect GND with the housing, screening or functional earth (FE)!

Tab. 3/3: Connecting the power supply to the motor unit

Closed-loop controlled DC motors have a much higher current
consumption during the switch-on or starting torque than in
rated operation. These consumers cause a brief overloading
of the power supply or a short circuit.
Power supply units with U/I output curve continue to provide
the full output current (at reduced output voltage) even in the
event of a higher load or short circuit.
With power units with additional output reserve (power
boost), the output voltage remains constant even during
overload. Power units with U/I characteristic curve and power
reserve are therefore optimally suited for universal industrial
use.