5. Commissioning

5-70

Festo P.BE-MTR-DCI-CO-EN en 1209a

Start/stop record

Nominal record
number
Output data

Stop
CCON.B1 (STOP)

Quit Start
SPOS.B1 (ACK)

Motion Complete
SPOS.B2 (MC)

Actual record
number
Input data

N - 1

N

N +1

N - 1

N

1

0

1

0

1

0

1

0

1

0

1

2

3

4

6

1

0

1

0

The axis moves
SPOS.B4 (MOV)

Start
CPOS.B1 (START)

N +1

5

1

Prerequisite:
“Quit Start” = 0

2

Rising edge at “Start” causes the new
record number N to be accepted and
“Quit Start” to be set

3

As soon as “Quit Start” is recognized
by the PLC, “Start” may be set to 0
again

4

The controller reacts with a falling
edge at “Quit Start”

5

As soon as “Quit Start” is recognized
by the PLC, the next record number
may be started

6

A currently running positioning task
can be stopped with “Stop”

Fig. 5/4:

Sequence diagram Start/stop record