3. Installation

3-6

Festo P.BE-MTR-DCI-CO-EN en 1209a

3.2

Earthing

Note

Connect the earth connection of the MTR-DCI with low
impedance (short cable with large cross-sectional area)
to the earth potential.

This prevents interference from electromagnetic sources
and ensures electromagnetic compatibility in accordance
with EMC directives.

In order to connect the MTR-DCI to the earth potential, use
only the following earth connection:

Earthing strap on the free end of the power supply cable,
see assembly instructions for cable KPWR-
MC-1-SUB-9HC-... (See chapter 3.3.2)

Caution
Earth or ground loops can make EMC safety measures
ineffective and allow high compensating currents to des-
troy the motor unit.

Connect

only the cable screen of the power supply cable

to the functional earth FE.

The GND connection must

not be made to the housing,

screening or functional earth FE!

Never connect one of the voltage connections (see
chapter 3.2, A1, A2) to FE or the housing.

This will avoid damaging the device and impairing protec-
tion against electromagnetic interference (EMC).