5. Commissioning
5-45
Festo P.BE-MTR-DCI-CO-EN en 1209a
CDIR
Control byte CDIR is a special control byte for the operating
mode “Direct mode.”
Control byte 3 (CDIR) – only Direct mode
Bit
EN
Description
B0
ABS
Absolute/
Relative
= 0: Nominal value is absolute
= 1: Nominal value is relative to last nominal value
B1
COM1
Control mode
= 00: Positioning mode (see also 5.5.7 point 6)
= 01: Power operation (see also 5.5.7 point 7)
= 10: reserved
= 11: reserved
B2
COM2
B3
CONT
–
reserved
:= 0
B4
VLIM
–
reserved
:= 0
B5
XLIM
Stroke (
X-)
limit not active
Power control
= 0: Stroke monitoring active
= 1: Stroke monitoring not active
B6
FAST
–
reserved
:= 0
B7
FUNC
–
reserved
:= 0