3. Installation
3-9
Festo P.BE-MTR-DCI-CO-EN en 1209a
Note the following selection criteria with the power supply of
the MTR-DCI:
–
The power unit rated current should correspond at least
to the motor starting current (peak current).
–
Motor tolerances with 20 % - 50 % output reserve should
be considered.
Voltage supply
MTR-…-32
MTR-…-42
MTR-…-52
MTR-…-62
Rated motor current
A
0.73
2
5
6.19
Peak motor current
A
2.1
3.8
7.7
20
Nominal current of power sup-
ply unit
A
≥ 3
≥ 6
≥ 10
≥ 15
1)
External fuse (secondary side)
A
5 A
slow-blowing
7 A
slow-blowing
10 A
slow-blowing
25 A
slow-blowing
1)
Exception
Tab. 3/4: Requirement for power units and fuses
1
External fuse
2
Earth connection
(see chapter 3.2)
A1
A2
A1
A2
Fig. 3/2:
Example of connection – Power supply