Festo Электромотор MTR-DCI User Manual

Page 194

Advertising
background image

6. Diagnostics and error display

6-10

Festo P.BE-MTR-DCI-CO-EN en 1209a

Fault

Possible cause

Remedy

CAN-BUS INIT NO
PARAMETER ERROR

Essential bus parameters not set.
– MTR-DCI not on the bus.

Set bus parameters (see sec-
tion 5.2.7):
– CAN Node-ID
– CAN bit rate
– CAN profile

CAN-BUS NO EXT. SUP-
PLY VOLTAGE

External CAN supply missing (only if
parameterised, see section 4.5.6,
Tab. 4/10 or object 2FF6h, sec-
tion C.3.4).

Check external CAN supply (see
section 3.6 or

Set internal CAN supply (see sec-
tion 5.2.7)

HARDWARE ERROR

Device fault (EEPROM defective, or
user data destroyed)

Contact Festo Service.

I2t-ERROR

Current monitoring i

2

t.

– The drive is blocked

Check the mechanical system of
the drive.

HOMING ERROR

Error during homing
– Homing run interrupted
– Reference switch defective

If necessary, check the function of
the reference switch.

It is essential that you repeat
homing.

LOAD-POWER-DOWN

Voltage monitoring
– Load voltage too low

MTR-DCI 32/42/52: U < 18 V
MTR-DCI 62: U < 34 V

– Voltage drops under load

Check the power supply:
– Power supply unit too weak?
– Supply line too long?

MOTOR STOP

Error during the positioning proced-
ure
– A positioning procedure is dis-

continued on the control panel
with EMERG.STOP (Taste
”Menu”).

Acknowledge the error on the
control panel with ”Enter”

OVERHEATING

Overheating
(Operating temperature > 80 °C).
– Temperature of power output

stage too high.

– Ambient temperature too high

Check:
– That the limits are complied

with (motor characteristic
curves),

– the mechanical system e.g. for

sluggishness.

If necessary, reduce the ambient
temperature.