C. Reference – CANopen and CI objects

C-66

Festo P.BE-MTR-DCI-CO-EN en 1209a

Controlword CiA 402

CI

6040h

– / 00h

Var

uint16

rw

Description

To modify the current controller status or trigger an action.
For description see section C.1.4.
Specific features when accessing via CI:
– Reset Fault (Bit 7) as per CiA 402 processing with positive edge, but level

evaluated via CI.

– Start bit (bit 4) in homing and positioning as per CiA 402 edge-triggered, but

for CI level evaluated. 0-set interpreted as stop.

– HMI access locked (bit 14) only accessible via fieldbus.
– Switching to “Operation enable” may simultaneously include action-trigger-

ing bits (start, jog, ...).

– Shortened status transitions:

– Command “Operation disable” or “Switch on” (same coding):

Status OPERATION ENABLE -> READY TO SWITCH ON.
Status READY TO SWITCH ON -> SWITCHED ON.

– “Disable voltage” command (bit 1 = 0, rest irrelevant) – all statuses

-> READY TO SWITCH ON.

– “Operation enable” command (all statuses) -> OPERATION ENABLE.
– “Voltage disable” and “Quick stop” commands -> READY TO SWITCH ON.

Statusword CiA 402

CI

6041h

– / 00h

Var

uint16

ro

Description

To modify the current controller status or trigger an action.
For description see section C.1.4.
Specific features when accessing via CI:
– Bit 4 in CI reversed polarity as with CiA 402.
– In the Fault status, when power is applied to the axis, the status is indicated

not as xxx8, but xxxA, meaning “Switched on” is set.