5. Commissioning

5-46

Festo P.BE-MTR-DCI-CO-EN en 1209a

5.5.6

Description of the status bytes SCON, SPOS, SDIR (RSB)

Status byte 1 (SCON)

Bit

EN

Description

B0
ENABLED

Drive

Enabled

= 0: Drive blocked, controller not active
= 1: Drive (controller) enabled

B1
OPEN

Operation
Enabled

= 0: Stop active
= 1: Mode enabled, positioning possible

B2
WARN

Warning

= 0: Warning not applied
= 1: Warning applied

B3
FAULT

Fault

= 0: No fault
= 1: There is a fault or fault reaction is active Fault code in the fault

buffer

B4
24VL

Supply Voltage
is

Applied

= 0: No load voltage
= 1: Load voltage applied

B5
FCT/
MMI

Drive Control
by FCT/MMI

= 0: Device control through PLC/fieldbus
= 1: Device control through FCT/MMI

(PLC control is

Locked)

B6
OPM1

Display

Opera-

ting

Mode

= 00: Record select (standard)
= 01: Direct mode
= 10: reserved
= 11: reserved

B7