RISCO Group ACUS User Manual

Page 344

Advertising
background image

User Manual for ACUS

Uncontrolled

when

printed

©

RISCO

Group

316

41. Select appropriate parameters. Here, select Deactivated. This indicates that the card

of the person (who will trigger the access denied event on the first floor) will be
deactivated. The person will not get access anywhere in the building unless he
contacts the required authority.

42. You may add one more condition which will be verified before executing the operation.

43. Select the Condition check box and click Condition. The Automation Condition

dialog box appears.

Note: The Condition check box must be selected to enable the condition.

Figure 327: Automation Condition

44. Select the Entity. For example, Sensor.

45. Select the required action from the Selection list. For example, select Any Sensors.

Figure 328: Select a Condition

46. Select the property as Status and its value as InActive. This indicates that the

operation will only be executed if any of the sensors is in inactive state.

47. Click Save. The message appears, “Automation saved successfully”.

48. You may click Test to verify if the automation is executed. The message appears,

“Automation Triggered Successfully”.

You may add as many operations as you want, depending upon your requirements.

This is one instance of adding automation. For more details on triggers, conditions and

operations, refer to the

ACUS Automation Manual.

14.3 Edit Automation

To make changes to the automation:

1. On the ACUS home page, click Settings

 Configuration  Automations. The

Automations dialog box appears.

Advertising