Procedure for preparing 24 v input cable – Yaskawa MP920 Motion Module User Manual
Page 171
Advertising
5.2 SVA-02A Module
5-29
5
Procedure for Preparing 24 V Input Cable
Use a twisted-pair cable with a wire size of AWG#24 to AWG#20 (0.2 to 0.51 mm
2
) to con-
nect the 24-VDC power supply to the 24-V input connector on the SVA-02A Module.
Use the following procedure to prepare cables.
1. Strip the wire of its covering for 6.5 mm from the end.
2. Secure the wire to the plug.
Insert the core wire deeply into the plug and tighten the screws to a tightening torque of
0.3 to 0.4 N·m.
Pin No.
Signal Name
Pin Name
2
24 V
+24 VDC Input
1
0 V
0 V
Core wire
Covering
6.5 mm
+ Side (pin No.2)
- Side (pin No.1)
Advertising