8 Troubleshooting

8.2.1 Alarm IL††22

8-18

„

Broken PG Wiring

SVA-01A

SVA-02A

SVB-01

PO-01

Supported

Supported

Not supported

Not supported

Detection Timing

• Enabled only in Position Control Mode, Phase Control Mode, and Zero Point Return Mode with

the pulse count system selected (A/B mode). The PG broken wire detection signal is monitored
in scan cycles through software.

Note: The PG broken wire detection signal is detected by a hardware circuit.

Alarm Processing

• Stop
• Position loop processing will be stopped and the machine will decelerate to a stop using the

open loop speed reference.

• The servo OFF command will be executed after decelerating to a stop.
• Create a user application that will set acceleration/deceleration time to 0 when a broken PG wire

is detected if you want to stop immediately rather than decelerating to a stop.

Errors and Causes

• Improper or disconnected encoder wiring.
• Encoder or SERVOPACK failure.
• SVA Module failure.

Action Taken

• Check the encoder wiring.
• Contact Maintenance.