6 SVB Module Specifications and Handling

6.1.2 Handling

6-4

Normal
operation

One of servo numbers 1 to 16 will be displayed.
The Servo Modules is operating normally.

Major fault

A two-digit error code appears following F.
Examples:
F

→ 0 → 1: Watchdog time over

F

→ 0 → 2: Synchronization error

F

→ 4 → 1: ROM diagnosis error

F

→ 4 → 2: RAM diagnosis error

F

→ 4 → 3: Shared memory diagnosis error

F

→ 4 → 8: General illegal instruction interrup-

tion occurrence

F

→ 4 → 9: Slot illegal instruction interruption

occurrence

F

→ 5 → 0: CPU address error interruption occur-

rence

F

→ 5 → 2: User brake interruption occurrence

F

→ 5 → 3: Trap instruction interruption occur-

rence

F

→ 5 → 5: CERF initializing error

F

→ 5 → 8: TLB error exception interruption

occurrence

F

→ 5 → 9: TLB error exception interruption

occurrence

F

→ 6 → 0: TLB disable exception interruption

occurrence

F

→ 6 → 1: TLB disable exception interruption

occurrence

F

→ 6 → 2: Initial page write in exception inter-

ruption occurrence

F

→ 6 → 3: TLB protective exception interruption

occurrence

F

→ 6 → 4: TLB protective exception interruption

occurrence

(cont’d)

Display

Category

Meaning

or

followed by error code

Advertising