2 Motion Control

2.4.4 Zero Point Return (ZRET)

2-58

„

DEC2 + Phase-C Pulse

This method is used to perform zero point return using a limit switch (deceleration limit
switch) and a zero point signal (Phase-C pulse) by rapid traverse using linear acceleration/
deceleration (without a dog width).

The limit switch is used with a mechanical configuration such as the one shown in the fol-
lowing illustration.

1. With this method, the axis recognizes the machine position by the deceleration limit switch ON/

OFF status, and automatically performs a return operation. Be sure to perform zero point return
under the same conditions.

2. With pattern (B), set the deceleration limit switch inversion selection (bit 10) of motion fixed

parameter No. 17 to ON.

Zero Point Return Operation Started with the Dog (Deceleration Limit
Switch) Signal in the High Area

SVA-01A

SVA-02A

SVB-01

PO-01

Available

Available

Not available Not available

Low

High

Deceleration
limit switch

Pattern (A)

Machine total
operating area

Reverse direction

Forward direction

Low

High

Deceleration
limit switch

Pattern (B)

Reverse direction

Forward direction

Machine total
operating area

INFO

1.

2.

5.

4.

3.

6.

Speed
reference

Rapid traverse speed

Dog
(deceleration limit switch)

Zero point signal
(Phase-C pulse)

Creep speed

Approach speed

Zero point

Zero point
return position

Time

Zero point return
final travel distance

Reverse direction

← → Forward direction

0