Filter type change error, Filter time constant change error – Yaskawa MP920 Motion Module User Manual

Page 370

Advertising
background image

8 Troubleshooting

8.2.1 Alarm IL††22

8-14

„

Filter Type Change Error

The command that is being executed will not stop even if an error occurs. A stop program is needed in
the user ladder logic program if you want to stop a command that is being executed.

„

Filter Time Constant Change Error

The command that is being executed will not stop even if an error occurs. A stop program is needed in
the user ladder logic program if you want to stop a command that is being executed.

SVA-01A

SVA-02A

SVB-01

PO-01

Not supported

Not supported

Supported

Not supported

Detection Timing

• Detected only when a motion command is used in Position Control Mode.

(Detected by the motion command processing section)

Alarm Processing

• Filter type change command will not be executed.
• Bit 5 (command error end) of IW††15 (Motion Command Status) will turn ON.

Errors and Causes

• With an interpolation command (interpolation or interpolation with the position detection), an

error will occur if the filter type change command is specified before distribution has been fin-
ished for the command (IB††153 OFF).

• The filter type change command will be ignored for positioning (POSITIONING, EXTERNAL

POSITIONING, STEP, FEED) and other commands. (An error will not occur.)

Action Taken

• Check the Distribution Completed (IB††153 ON) status and then revise the program that exe-

cutes the filter type change command.

SVA-01A

SVA-02A

SVB-01

PO-01

Not supported

Not supported

Supported

Not supported

Detection Timing

• Enabled only when a motion command is used in Position Control Mode.

(Detected by the motion command processing section)

Alarm Processing

• The command will not be executed.
• Bit 5 (command error end) of IW††15 (Motion Command Status) will turn ON.

Errors and Causes

• With an interpolation command (interpolation or interpolation with the position detection), an

error will occur if the filter time constant change command is specified before distribution has
been finished for the command (IB††153 OFF).

• The filter time constant change command will be ignored for positioning (POSITIONING,

EXTERNAL POSITIONING, STEP, FEED) and other commands. (An error will not occur.)

Action Taken

• Check the Distribution Completed (IB††153 ON) status and then revise the program that exe-

cutes the filter time constant change command.

INFO

INFO

Advertising