Operation with priority on display processing – IDEC High Performance Series User Manual

Page 1238

Advertising
background image

2 Digital I/O Units

29-4

WindO/I-NV2 User’s Manual

Operation with priority on display processing

When an external input occurs

Display processing
Parts placed on the screen are processed in order from the top down. This process constitutes a single scan.
When processing reaches the end, it returns to the beginning and starts the next scan.
The time for one scan depends on the number and type of parts used, as well as how they are configured.

Input refresh
Inputs are refreshed every 10 ms independent of the screen scan.
However, inputs at the digital I/O unit are not reflected in the HG Digital Input (LEX) until the screens scan ends.

Input delay
When an external input occurs on the digital I/O unit, the delay time until the input is reflected in the HG Digital Input
(LEX) will be at least 5 ms or a maximum of 15 ms + the scan time (HG special registers LSD 4).
The longer display processing takes, the longer the delay.

Control processing

Digital I/O unit input

Input

refresh

LEX

X

10 ms

Input

refresh

10 ms

Input

refresh

10 ms

Scan time

Input delay

Input

delay

Start of scan

Display

processing

1 scan

External input

X

External input

HG Digital Input

End of scan

Input delay is longest when an input occurs on the digital I/O unit
immediately after the scan begins because it does not get reflected
in the HG Digital Input (LEX) until the beginning of the next scan.

LEX

X

Input

refresh

Display

processing

1 scan

HG Digital Input

External input

Input delay

(maximum)