3 properties of timer dialog box, General tab, Properties of timer dialog box -59 – IDEC High Performance Series User Manual

Page 795: Commands

Advertising
background image

WindO/I-NV2 User’s Manual

12-59

7 Timer

12

Commands

7.3 Properties of Timer Dialog Box

This section describes items and buttons in the Properties dialog box.

General Tab

Part Name
Enter a name for the part. The maximum number is 20 characters.

Timer Address
Specifies the HG timer address (0 to 31).
The device type for the HG timer relay is LTC. The device type where the current value is stored is LTD.

Unit
Select the unit of time from sec or 100 msec.

Preset Value
Select the data type to use and the enter the preset value.
The preset value is the time from when the timer starts its countdown until 1 is written to the HG Timer Relay LTC.

Example: When 0 is specified for Timer Address

HG Timer Relay:

LTC 0

HG Timer Current:

LTD 0

Value:

When selecting sec in Unit, the preset value is specified with 1 to 65535 (second units) up to a maximum
of 1092 minutes 15 seconds.
When selecting 100 msec in Unit, the preset value is specified with 1 to 65535 (100 msec units).

Device:

Uses word device values.
Specify the Device Address.

Click

to display the Device Address Settings dialog box. For the device address configuration

procedure, refer to Chapter 2 “5.1 Device Address Settings” on page 2-67.