2 line chart, Windo/i-nv2 user’s manual ■ scroll – IDEC High Performance Series User Manual

Page 698

Advertising
background image

2 Line Chart

11-26

WindO/I-NV2 User’s Manual

Scroll

*3

*1 HG2G-5F, HG3G/4G only
*3 Advanced mode only

Control Display Update and Scrolling: To scroll the chart to display past data and to display the cursor, the chart

display updating must be stopped. To control updating the display, select this
check box and specify the bit device or bit of the word device to control the
display.

Click

to display the Device Address Settings dialog box. For the device

address configuration procedure, refer to Chapter 2 “5.1 Device Address
Settings” on page 2-67
.
Display updating stops when the device value changes from 0 to 1. Display
updating restarts when the device value changes from 1 to 0.
This option can only be configured when Log Trend (Normal) or Log Trend
(Pen Recorder)
is selected for Chart Type.

Right Scroll Device, Left Scroll Device: The chart can be scrolled to the right or to the left when display updating is

stopped. This option specifies the bit device or bit of the word device to scroll
the chart left or right.

Click

to display the Device Address Settings dialog box. For the device

address configuration procedure, refer to Chapter 2 “5.1 Device Address
Settings” on page 2-67
.
The chart scrolls right or left one point of data each time the device value
changes from 0 to 1.
These options can only be configured when the Control Display Update and
Scrolling
check box is selected.

Display cursor

*1

:

The cursor can be displayed when display updating is stopped. The cursor is
displayed on the chart. Select this check box to display the cursor. The Date
and Time (Cursor)
tab is displayed where the functions related to the cursor,
such as the cursor style and display position control, can be configured.
This option can only be configured when the Control Display Update and
Scrolling
check box is selected.

1

0

Right scroll device

LM 0 value

0

20

40

60

80

100

-20

120

0

20

40

60

80

100

-20

120

0

20

40

60

80

100

-20

120

0

20

40

60

80

100

-20

120

Scroll right

1 data point

Stop updaƟng

Scroll right

1 data point

Scroll right

1 data point

Stop updaƟng,

then scroll right

3 data points