1 bar chart – IDEC High Performance Series User Manual

Page 682

Advertising
background image

1 Bar Chart

11-10

WindO/I-NV2 User’s Manual

When Data Over
These options configure the operation of the part when the allowable range is exceeded.
These options can only be configured when the Minimum or Maximum check boxes are selected under Range.

Example: If the word device value of the reading source is “110” which is higher than the upper limit of “100” ,or

“-10” which is below the lower limit of “0”, a value of 1 will be written to LM0 and the displayed bar will
flash.

Flash:

Select this check box to make the chart flash when the displayed data exceeds the allowable range.

Report:

Select this check box to write 1 in the report device when the displayed data exceeds the allowable
range.

Report Device: Specifies the report device.

Click

to display the Device Address Settings dialog box. For the device

address configuration procedure, refer to Chapter 2 “5.1 Device Address Settings” on
page 2-67.

Ch1 data

60

Ch2 data

Ch1
Ch2

10

1

0

0

1

Display

20

110

50

80

10

-10

Flashing

Flashing

Range: Value

Minimum: 0

Maximum: 100

When Data Over

Flash

Report

DesƟnaƟon Device: LM0

Data over noƟficaƟon: LM0

100

50

0

100

50

0

100

50

0

100

50

0