background image

4 HG2F

34-50

WindO/I-NV2 User’s Manual

Serial interface 2

• Connect pin 6(EN) and pin 2(ER) unless performing maintenance communications for downloading project data.

Expansion Unit Interface (EXT)

The HG2F can be used in conjunction with dedicated HG Series option units. Refer to the Expansion Unit instruction
manual for details.

O/I Link Interface

The HG2F Operator Interface can be connected to an O/I Link Unit for 1:N communication with a PLC. This allows
high-speed communication with the PLC host.

Interface Specification

RS232C

Connector

Mini DIN 8 pin

No.

Name

I/O

Function

1

RS

OUT

Request to Send

2

ER

OUT

Data terminal ready

3

SD

OUT

Send Data

4

RD

IN

Receive Data

5

DR

IN

Data set ready

6

EN

IN

Use set ready

7

SG

Signal Ground

8

NC

No connection

6

3

4

7

8

5

2

1