Alarm log function – IDEC High Performance Series User Manual

Page 837

Advertising
background image

WindO/I-NV2 User’s Manual

13-39

4 Using Data and Detected Alarms

13

Alarm Log Function

Real Time
Real time output displays the alarm state and the time the alarm became that state on a single line each time an
alarm occurs, is recovered from, or is confirmed.
The data structure of files output with real time output is as follows. Bold items are replaced by the Alarm Log
settings, sampled data, project file name, and WindO/I-NV2 version.

Headers

"Project Name","Project name","Version number"
"File Type","Log type"
Blank row

Title row

"Time","State","Ch.No.","Message"

Data row

" MM/DD/YYYY HH:MM:SS","State"," Channel number","Message"

Output example

Data size of each row

"Project Name","Dimmer Console","V4.50"

- 41 bytes

"File Type","Alarm Log Data"

- 30 bytes
- 2 bytes

"Time","State","Ch.No.","Message"

- 35 bytes

" 08/11/2011 14:46:12","Occurred"," 1-0","Voltage drop"

- 57 bytes

" 08/11/2011 14:46:13","Recovered"," 1-0","Voltage drop"

- 58 bytes

" 08/11/2011 14:46:16","Confirmed"," 1-0","Voltage drop"

- 58 bytes

" 08/11/2011 14:47:18","Occurred"," 1-1","Temperature abnormal"

- 65 bytes

• The data size for each row is counted as 2 bytes for full-width characters, 1 byte for half-width characters,

and 2 bytes for newlines. The total for each row is the total amount of space for the file.

• A space is inserted before the date in the data row.
• The display type for the date and time varies based on the language configured in Project Settings, on

the Project Details tab, in Language.

Japanese: YYYY/MM/DD HH:MM:SS
European, Chinese, Taiwanese, Korean, Central European, Baltic, Cyrillic: MM/DD/YYYY HH:MM:SS