1 Error Messages

35-2

WindO/I-NV2 User’s Manual

ZNV file is not found

The project file (ZNV format) was not in the specified location
on the external memory device when a download was made
using the Project Data Transfer function.

Check whether or not the file is in the
specified location on the external
memory device.

ZLD file is not found

The PLC Program file (ZNV format) was not in the specified
location on the external memory device when a download was
made using the PLC Program Transfer function.

Check whether or not the file is in the
specified location on the external
memory device.

ZNV file format Error

When a download was made using the Project Data Transfer
function:

• The project file is not in ZNV format.
• The file is corrupt.

Remake the project file (ZNV format).

ZLD file format Error

When a download was made using the PLC Program Transfer
function:

• The PLC Program file is not in ZLD format.
• The file is corrupt.

Remake the PLC Program file (ZLD
format).

O/I type is not correct

When a download was made using the Project Data Transfer
function, the model of the downloaded project and the model of
the destination MICRO/I were different

Check that the model name that is set
in the file you want to download is the
same as the model name of the
destination MICRO/I.

PLC Type is not correct

When a download or upload was made using the PLC Program
Transfer function:

• The model of the downloaded PLC Program and the model

of the destination PLC were different.

• The runtime program version using the downloaded PLC

Program and the one of the destination PLC were different.

Check PLC models and runtime
program versions.

PLC Password is not valid When a download or upload was made using the PLC Program

Transfer function, the password you entered was incorrect.

Enter the correct password.

PLC communication Error When a download or upload was made using the PLC Program

Transfer function, a communication problem with the PLC
occurred.

It is possible that there is a problem
with the connection with the PLC.
Check the connection between
MICRO/I and the PLC.

The specified files are not
found

The specified files were not in the specified location on the
external memory device when the File Copy function was
executed.

Check whether or not the file is in the
specified location on the external
memory device.

File Size Error

The size of the source file exceeded the limit when the File Copy
function was executed.

Check the source file size. For the
maximum file size that can be copied,
refer to Chapter 28 “3.5 Precautions”
on page 28-40.

Script error

An error occurred for a process in execution of the script.

Check the value of LSD52 and LSD53,
and correct the script. For details,
refer to Chapter 20 “Script” on page
20-1.

Device write error

The script generated a lot of write data, and the write operation
failed.

Reduce the number of write
operations to be performed at the
same time.

Insufficient memory
error

The resource memory of the HG is insufficient because of the
use of a large number of the following parts.

• Pilot Lamps, Multi-State Lamps, and Picture Displays with

the “Recover Background” checkbox is selected.

• Message Display, Message Switching Display, and Alarm List

Display with the “Scroll” checkbox is selected.

• Line Chart with the “Display cursor” checkbox is selected.
• Parts over the number limit of parts that can be set per

screen by overlapping Base Screen.

Clear the “Recover Background” ,
“Scroll” or “Display cursor” checkbox,
or delete parts to reduce memory
resource utilization.

Indirect device error

Indirect read and indirect write failed when using the Word
Button or Word Write Command.

Do not execute indirect read and
indirect write to host device while
LSM14 or LSM15 is ON.

Check Interface settings MICRO/I cannot change into the Run mode because the

Interface settings are not correct.

Download the project data after
modifying the Interface settings in by
selecting [Configuration] - [System
Setup] - [Project] - [Communication
Interface]tab from the WindO/I-NV2
menu.

Network off-line

This error message is only displayed when O/I Link is being
used.

See the External Device Setup Manual
for details.

Error Message

Cause

Solution