Connector pin functions, Construction of contact, Micro/ i specif ication s – IDEC High Performance Series User Manual

Page 1393: On off

Advertising
background image

WindO/I-NV2 User’s Manual

34-77

6 HG2S

34

MICRO/

I Specif

ication

s

Connector Pin Functions

Construction of Contact

1. Emergency stop switch or Stop switch (Direct opening action) (A1, A2)

Emergency stop switch or stop switch is available to connect to an emergency stop circuit. It remains locked when
operated. Contacts do not open the operator is locked (safety locking mechanism). Direct opening circuit function
ensures to open contacts even if contacts are welded.

2. Enabling switch (Direct opening action) (B1, B2)

The enabling switch consists of two contacts (OFF-ON-OFF). They can be wired so that the contacts can be monitored
mutually using two input points. Each contact works independently, so the end of the switch at operation, a time
difference between the two contacts may occur. Wire the enabling switch so that the contacts can be mutually
monitored using two input points. Design a sequence program in consideration of the time difference.

No.

Name

Function

1

FG

Frame ground

2

NC

3

A1

A1 Emergency stop SW or Stop SW

4

5

A2

A2 Emergency stop SW or Stop SW

6

7

24V DC+

Power supply input

8

24V DC+

Power supply input

9

24V DC-

Power supply ground

10

24V DC-

Power supply ground

20

B1

B1 Enabling Sw

21

22

B2

B2 Enabling Sw

23

24

D1 NO1 (C1 NO2)

D1 Contact 1 (C1 Contact 2)

25

D2 NO1 (C2 NO2)

D2 Contact 1 (C2 Contact 2)

26

C1 NO1 (D1 NO2)

C1 Contact 1 (D1 Contact 2)

27

C2 NO1 (D2 NO2)

C2 Contact 1 (D2 Contact 2)

28

SW COM

C1, C2, D1, D2 common

4

6

3

5

A1

A2

D-sub 37P

Pin No.

[Action of the enabling switch]

3 positon

(OFF-ON-OFF)

B1

B2

21

23

20

22

D-sub 37P

Pin No.

OFF

ON

OFF

Push
lightly

Release

Push
further

Release