IDEC High Performance Series User Manual

Page 232

Advertising
background image

3 Project Settings Dialog Box

4-46

WindO/I-NV2 User’s Manual

Ignore communication errors and continue operation

*1

Select this check box to continue MICRO/I operation even when a communication error occurs.
This option is only displayed when the host I/F driver Connection is 1:N Communication.

*1 HG2G-5F, HG3G/4G only

Display error message:

Select this check box to display an error message (host communication error) when a
communication error occurs and operation continues. Ack is displayed on the error
message (host communication error).
When the Ignore communication errors and continue operation check box is
cleared, Ack is not displayed on the error message.

Auto retry:

Select this check box to automatically retry communication from the MICRO/I to the
station number where the communication error occurred when a communication error
occurs and operation continues.
All other communication stops while retrying.

To manually retry communication, clear the Auto retry check box.
To retry all station numbers, write 1 in bit 1 (initialize) of the device address configured by Batch
monitoring the communication error information for all Station Numbers
.
To individually retry communication, write 1 in bit 0 (connection setting) of the device address configured by
Monitoring communication error information for each station, individually.

Batch monitoring the communication error information for all Station Numbers:

Specifies the device that stores communication error information for all station numbers.
Only an HG internal register can be configured for this option.

Click

to display the Device Address Settings dialog box. For the device address

configuration procedure, refer to Chapter 2 “5.1 Device Address Settings” on page 2-67.
The information stored as error information is as follows. For details, refer to the External
Device Setup Manual.

• Initialization
• Conditions under which the error occurred
• Read error history
• Write error history

Monitoring communication error information for each station, individually:

Select this check box to store the error information for each station number in devices.

Total number of station being monitored: Specifies the number of station numbers for

external devices.

Status Device:

Specifies the device that stores communication
error information for each station number. Only
an HG internal register can be configured for
this option.

Click

to display the Device Address

Settings dialog box. For the device address
configuration procedure, refer to Chapter 2
“5.1 Device Address Settings” on page 2-67.
This error information utilizes a maximum of
256 devices. Use caution so that the used
addresses do not overlap with other addresses.
The information stored as error information is
as follows. For details, refer to the External
Device Setup Manual.

• Connection settings
• Conditions under which the error occurred
• Read error history
• Write error history

Advertising