IDEC High Performance Series User Manual

Page 860

Advertising
background image

3 Data Log Settings Dialog Box

14-22

WindO/I-NV2 User’s Manual

Real Time
Select this check box to output data to the memory card in real time.

With real time output, data is saved to the memory card in three minute intervals after the MICRO/I starts running. For
the HG2G-5F and the HG3G/4G, if the accumulated data reaches 80% of the amount set in the Data Storage Area, then
the data is forcibly saved to the memory card. When there is already data with the same file name on the memory card,
data is appended to that file. If there was no update to the data during the three minutes, it is not output. Data is
appended to the file until the size of the file reaches the restriction size (256 MB), so the maximum amount of output
data differs according to the settings for the output channel such as the amount of data, the data size, and the labels.

If the sampling interval is shorter than real time output (the interval for writing to the memory card), that Data Log is recorded
up to the data storage amount - 1, and then afterwards, old data is discarded in order and replaced with new data.

*1 Advanced mode only
*2 HG2G-5F, HG3G/4G only

MICRO/I

Data Log data (CSV)

Output to

memory card

Memory Card

Data Log data

Sampling

Time

Data001

Data002

Data003

01/01/2011

12:00:30

20

120

201

01/01/2011

12:01:30

21

121

204

01/01/2011

12:02:30

22

122

206

01/01/2011

12:03:30

23

123

206

01/01/2011

12:04:30

24

124

210

01/01/2011

12:05:30

25

125

210

01/01/2011

12:06:30

26

126

218

Data to be output
3 minutes aŌer
operaƟon starts

Data to be output
3 minutes aŌer that

Data to be output
aŌer another
3 minutes

3 minute interval

aŌer operaƟon

starts

Real time output stops when the file size of the Data Log data exceeds 256 MB or when there is insufficient
space on the memory card. Memory card error information is stored in HG special register LSD42.

• When the value of HG special relay LSM20 changes from 0 to 1, the data at that time is first output in real

time to the memory card, and then access to the memory card is stopped.

• The text font configured for the starting device is output as the label font.

• You can check the free space on the memory card with HG special registers LSD43 to 44.

File Name:

Enter the file name for the output data or shows the file name.

HG2G-5F, HG3G/4G:

The default is “LOGOn.CSV”. (n: Data log channel number)
To change the file name, enter a new file name. The maximum number
is 120 characters (including the extension).

HG2F/3F/4F:

The file name is “LOGOn.CSV”. (n: Data log channel number)
This cannot be changed.

Specify File Name by Value of Device

*1*2

:

Select this check box to specify the name of the file for the output data with the value of the
device configured by (File Name Device).
(File Name Device):

Specifies the word device that is the source of the data to use as the file
name. The file name is set by reading the values sequentially from the
starting device specified with the file name device and handling those
values as character data up to the character before NULL (00).
The maximum number of devices is 40 (80 single-byte characters). You
can only specify an internal device. For the device address configuration
procedure, refer to Chapter 2 “5.1 Device Address Settings” on page 2-
67
.

Example: When the device specified by (File Name Device) is LDR100 and the text to set is "IDEC":

The file name at this time becomes "IDEC.CSV".

LDR100
LDR101
LDR102

(File Name Device)

4844

(Hex)

4543

(Hex)

‘ I ’ ‘D’

‘E’ ‘C’

0000

(Hex)

(NULL)

Advertising
This manual is related to the following products: