IDEC High Performance Series User Manual

Page 138

Advertising
background image

5 User Communication

3-36

WindO/I-NV2 User’s Manual

Command Size
Displays the data size of a configured command.
The calculation method for command size varies based on the type selected in Command Type on the Command
Settings dialog box. The command size calculation methods are as follows.

OK
Save the settings.

Cancel
Cancel the saving of settings.

BCC:

Displays the specified data enclosed in BCC ( ).
BCC(Calculation Start Position Calculation End Position Calculation Type
Conversion Type Number of bytes)

Calculation Start Position:

Displays the data position where the BCC calculation
starts.

Calculation End Position:

Displays the data position where the BCC calculation ends.

Calculation Type:

Display the methods to calculate the data between the
Calculation Start Position and Calculation End Position as
follows.
XOR: When XOR is selected
ADD: When ADD is selected
ADD2: When ADD (2's Complement) is selected

Conversion Type:

Display the conversion methods for values of devices as
follows.
B16-A: When Binary (HEX) to ASCII is selected
N: When No Conversion is selected

Number of bytes:

Displays the number of bytes of the transmitted or
received data.

Example: BCC(2 1 XOR N 2)

Skip:

Displays the specified data enclosed in Skip( ).
Skip(Number of bytes)
Example: Skip(2)

Edit

Add or change data.
To add data, select an empty line in the Command, and then click this button. To
change data, select data in the Command, and then click this button. For details, refer
to “Data Settings Dialog Box” on page 3-37.

Insert

Insert data at the position of the selected command.
Click this button to display the Data Settings dialog box. And specify the data. The data
at the insertion point shifts down by 1 item. When 32 data items are already set, you
cannot insert data.

Delete

Deletes the selected data.

Up

Shifts the selected data upward in the command.

Down

Shifts the selected data downward in the command.

TXD:

Number of bytes for Constant Data + Number of bytes for a data of Registering Constant + Number of
bytes of BCC + Number of bytes of Device x Words of Device

RXD:

Number of bytes for Constant Data + Number of bytes for a data of Registering Constant + Number of
bytes of BCC + Number of bytes of Skip + Number of bytes of Device x Words of Device

Advertising
This manual is related to the following products: