Beep tab, Alarm log function – IDEC High Performance Series User Manual

Page 827

Advertising
background image

WindO/I-NV2 User’s Manual

13-29

3 Alarm Log Settings Dialog Box

13

Alarm Log Function

Beep Tab

The Beep tab is used to configure whether or not the MICRO/I’s internal buzzer operates.

Beep when Alarm occurs
Select this check box to sound a beep when an alarm has occurred.

Stop Beep

*1

Select the check box for the items that will trigger the beep to stop.

*1 Advanced mode only
*2 The first alarm that has occurred in a state where no alarms are active

HG3G

HG2G-5F

HG2G-5S

HG2G-S

HG4G HG1F HG2F HG2S HG3F HG4F

Beep only First Alarm

*1

:

Select this check box to sound a beep only when the first alarm

*2

has

occurred.
No beeps will sound when another alarm is already active. Clear this
check box to sound a beep each time an alarm occurs.

Stop when touch everywhere on the screen: The beep stops when you touch anywhere on the screen.

Stop when press CHECK/All Chk. button:

The beep stops when you touch the key buttons CHECK or All Chk. on
the Alarm Log Display.

Stop when all Alarms are recovered:

The beep stops when all the alarms are recovered from.

• While the beep is sounding, System Area 1 address + 1 bit 6 is 1.
• To stop the beep when an alarm has occurred, use the following methods.

- Press the key button Stop Beep
- When a condition selected with the Stop Beep check boxes is satisfied
- Set System Area 1 address + 1 bit 6 to 0.
However, when 1 is written to System Area 1 address + 1 bit 6 for a reason other than the occurrence of
an alarm, the beep does not stop until 0 is written.