background image

2 Digital I/O Units

29-6

WindO/I-NV2 User’s Manual

Operation with priority on control processing

Input refresh
Inputs on the digital I/O unit are reflected in the HG Digital Input (LEX).

Input delay
There is a delay between the digital I/O unit input and the internal device HG Digital Input (LEX). The minimum delay
is 5 microseconds, and the maximum delay period is calculated by the amount of 5 microseconds and the execution
period.

I/O control
The script specified as the Cyclic Script executes during I/O control.

Output refresh
HG Digital Output (LEY) are output to the digital I/O unit.

Cyclic

Script

Display

processing

Input refresh

Output refresh

LEX

LEY

X

I/O control

Sleep

(Display

processing

executed)

End of processing

for part at bottom

of screen

Start of processing

for part at top

of screen

Execution Period

Execution

Period

External

input

Y

External

output

HG Digital Input

HG Digital Output

Input delay

Output

delay

Execution Period

When an input occurs in the digital I/O unit immediately after the
input refresh ends, the input delay will be the longest because the
processor waits for the input refresh in the next scan before reflecting
the input to the HG Digital Input (LEX).

LEX

X

Input refresh

Output refresh

I/O control

Sleep

(Display

processing

executed)

Input refresh

Output refresh

I/O control

Input delay

(maximum)

HG Digital Input

External

input