WindO/I-NV2 User’s Manual

10-23

1 Numerical Input

10

Data Displa

ys

Without Pressing the Numerical Input, Directly Entering Values from a Keypad on the Same Screen
Arrange a Numerical Input and a keypad on the same screen. In the properties dialog box for the Numerical Input, on
the General tab, under Keypad, select Current Screen for Type and select the Always Entry Mode check box.

1.5 Advanced Usage

Using the System Area

• When finished entering a value by pressing ENT, 1 is written to the System Area 2 Numerical Input Setting

Complete bit (address+3, bit 0).

• When CAN is pressed, entry mode is canceled and 1 is written to the System Area 2 Numerical Input Setting

Cancel bit (address+3, bit 1). However, if the keypad is closed by pressing

(close) on the popup screen's title

bar or another Numerical Input is pressed before finished entering the value by pressing ENT, entry mode is
canceled and 1 is not written to the System Area 2 Numerical Input Setting Cancel bit (address+3, bit 1).

• To clear the System Area 2 numerical input setting complete bit or the numerical input setting cancel bit, write 1 to

System Area 1 Numerical Input Setting Clear bit (address+1, bit 10). To automatically clear these bits when the
Numerical Input keypad is pressed in entry mode, select the Clear Keypad bit in System Area automatically
check box on the System tab in the Project Settings dialog box.

Host

MICRO/I

999

1234

D100:

1234

D100:

999

999

D100:

999

Write value

to device

Press ENT

Display value of device

(Entry mode)

Display value of device

(Entry mode)

Display value of device

(Entry mode)

Enter "999"

If the System Area 2 numerical input setting complete bit is set to another function's execution condition,
that function can be executed when ENT is pressed.
Example: To simultaneously close a popup screen when ENT is pressed

In the Properties of Goto Screen Command dialog box, on the General tab, select Close Popup
Screen
for Action Mode. On the Trigger Condition tab, select Rising-edge for Trigger
Type
, and configure Device as the System Area 2 Numerical Input Setting Complete bit
(address+3, bit 0).