2.4 External Interfaces

Serial Interface (COM1)

CAUTION

• Make sure to turn off the power to the HG2G-5F, HG3G/4G before wiring each interface or

switching the terminating resistor selector Switch.

• Note that only one of the RS232C or RS485(422) interfaces can be used at one time. Wiring both

interfaces will result in failure of the HG2G-5F, HG3G/4G. Wire only the interface used.

Interface Specification

RS232C/485(422)

Connector

D-sub 9 pin (Plug)

Screw lock bracket

Inch Screw Thread #4-40 UNC

No.

Name

I/O

Function

Communication type

1

4W-RDA/2W-A

IN/INOUT

Receive Data (+) [4W]/ Send and Receive Data (+) [2W] RS485(422)

2

RD

IN

Receive Data

RS232C

3

SD

OUT

Send Data

RS232C

4

4W-SDA

OUT

Send Data (+) [4W]

RS485(422)

5

SG

-

Signal Ground

-

6

4W-RDB/2W-B

IN/INOUT

Receive Data (-) [4W]/ Send and Receive Data (-) [2W]

RS485(422)

7

RS

OUT

Request to Send

RS232C

8

CS

IN

Clear to Send

RS232C

9

4W-SDB

OUT

Send Data (-) [4W]

RS485(422)