IDEC High Performance Series User Manual

Page 348

Advertising
background image

2 Word Button

8-24

WindO/I-NV2 User’s Manual

Data Type
Select the data type to be handled by the operation selected for Action Mode.

For details, refer to Chapter 2 “1.2 Available Data” on page 2-2.

BIN16(+) and BIN32(+) can only be set if Action Mode is set to OR, AND, or XOR.

Source 1
Specify the source word device.
Click

to display the Device Address Settings dialog box. For the device address configuration procedure, refer

to Chapter 2 “5.1 Device Address Settings” on page 2-67.

This setting is enabled only if Action Mode is set to Add, Sub, Multi, Div, Mod, OR, AND, or XOR.

Source Data
Select the data to be handled by the operation selected for Action Mode.

*1 Advanced mode only

BIN16(+) and BIN32(+) can only be set if Action Mode is set to Move. Because the number of devices
to transfer is specified in Advanced mode, you do not need to set Data Type.

If BCD4, BCD8 or float32 is selected and the arithmetic data contains a value inexpressible in BCD, a 1 is
written to the System Area 2 Arithmetic error bit (address+2, bit 5) and an error message is displayed.
For details, refer to Chapter 4 “Arithmetic error” on page 4-34.

Value:

Use a constant.

Only a Value can be handled if Action Mode is set to Set, Momentary, or Alternate.

If Action Mode is set to Momentary or Alternate, the value in the ON Data is written when the button

is ON, and the value in the OFF Data is written when the button is OFF.

Hexadecimal:

Select this check box to enter the ON Data and OFF Data values in
hexadecimal.

Device: Use a word device.

Specify the device.
Click

to display the Device Address Settings dialog box. For the device address configuration

procedure, refer to Chapter 2 “5.1 Device Address Settings” on page 2-67.

Use Reference Device

*1

: Select this check box and specify a device to change the source word device

according to the value of the specified device.

This setting is enabled only if Action Mode is set to Move.

For details, refer to Chapter 2 “Indirect Read and Indirect Write Settings” on page

2-5.

Transfer

*1

Specify the number of word devices (1 to 64) to transfer.

This setting is enabled only if Action Mode is set to Move.

Example: If Transfer is set to 2 and Write is set to 3, the same data in 2

continuous word devices will be written to the destination device 3 times.

:

Device: LDR0

Write: 3

999

LDR0

Destination Device: D100

D100

D101

D102

D103

Transfer: 2

1000

LDR1

D104

D105

999

1000

999

1000

999

1000

Advertising