background image

WindO/I-NV2 User’s Manual

3-69

5 User Communication

3

Communic

ation

5.4 Example of User Communication Settings

This section describes examples of user communication settings and command operations.

Example 1

This section describes an example of user communication protocol settings for creating the following commands and
command operations.

• Transmission command for transmitting data using Constant (Hexadecimal), Constant (Character), Device,

Constant (Hexadecimal) command settings when the trigger condition device changes to 1

• Receive command for receiving, processing, and storing data in devices, using Constant (Hexadecimal), Constant

(Character), Device, Constant (Hexadecimal) command settings, for data transmitted from an external device,
when the trigger condition device is 1

User Communication Settings dialog box settings

Transmission command: Command Settings dialog box settings

Operation for transmission command

1

Write a value of 100 (DEC) to LDR100 of transmission command data Device.

2

Change the trigger condition LM100 from 0 to 1 to start command transmission.
After the transmission wait duration (five seconds), the transmission data is sent. The transmission data is as follows.

• When data transmission is successfully completed, the Completed Device LM101 changes to 1.
• When the value of each bit of address+0 for Status Device LDR110 is 0, transmission is completed without an error.

Item

Setting

Protocol Name

Sample 1

Receiving Character Time Out

30 (×100 msec)

Item

Setting

Comment

TXD command

Command Type

TXD

Completed Device

LM101

Status Device

LDR110

Transmission Wait

50 (×100 msec)

Trigger Condition

While ON, Device: LM100

Command
Data Settings dialog box settings

Constant
(Hexadecimal)

'05'

Constant
(Character)

"D"

Device

Conversion Type: Binary (DEC) to ASCII,
Number of bytes: 4, Words: 1
Device: LDR100

Constant
(Hexadecimal)

'0D'

D

(44h)

0

(30h)

0

(30h)

0

(30h)

EQN

(05h)

1

(31h)

CR

(0Dh)

Transmission data:

Constant

(HEX)

Constant

(Character)

Device

Command settings:

Constant

(HEX)